HONEYWELL TF428WNM/U (WHITE) (Modbus RTU) COMMUNICATING DIGITAL THERMOSTAT (220/230VAC, 50/60HZ)

Previous 7 / 22 Next

HONEYWELL TF428WNM/U (WHITE) (Modbus RTU) COMMUNICATING DIGITAL THERMOSTAT (220/230VAC, 50/60HZ) Honeywell Temperature Display / Controller


THIS MODEL IS INVALID

HONEYWELL TF428WNM/U (WHITE) (Modbus RTU) COMMUNICATING DIGITAL THERMOSTAT (220/230VAC, 50/60HZ)

Note

TF428WNM & TFM428KNM are interchangeable, they do the same thing.

General
 
The TF428WNM/U communicating thermostat is designed for 3-speed fan and valve control in a fan coil system, including:
 
 2-pipe cool only/heat only/manual changeover
 4-pipe cool /heat manual / automatic changeover
 Ventilation mode
 Manual or automatic 3-speed fan control
 Water valve on/off control
 
The TF428WNM/U is available in Modbus RTU protocol and can be easily integrated into building automation system.
Features

 RS485 interface in Modbus RTU slave mode
 Memorized time off
 Cycle Per Hour (CPH)
 Random startup
 LCD display with simple user interface
 Room temperature or setpoint temperature display  selectable
 Manual or automatic fan speed selectable
 Temperature units in either °C or °F
 User setting can be stored when power loss
 Freeze protection function available
 Keypad lock options

Specifications
 
Physical Layer EIA485
Protocol Modbus RTU
Baud rate 4800/9600(Default)/19200
Parity None
Error Checking Mechanism CRC
Rated Power & Frequency 220/230VAC, 50/60Hz
Power consumption <2W
Control PI, On/off output
Accuracy ±1°C at 21°C
Auto Cycle times 100,000 times
Manual Cycle times 10,000 times
Protection class IP20
Set point range 10 ~ 32°C
Display range 0 ~ 37°C
Ambient operating limits 0~ +49°C
Ambient storage limits -30 ~ +60°C
Humidity limits 5~90% RH, non-condensing
Action Type: 1
Pollution Degree 2
Protection against electric shock class Class II
Electronic control software class Class A
Rated Impulse Voltage: 2500V
Maximum Temperature for 155°C
Relay wiring
Wire Sectional area
(Recommendation) 1.0~1.5mm2
Applied altitude up to 2000m above sea level
Rating Capacity
Working current for the whole product : 4(3)A
4A: When the load of the thermostat is resistance
3A: When the load of the thermostat is inductance
For Fan load 3(2)A
3A:when the load is resistance; 2A:When the load is inductance
For Valve load 2(1)A
2A: when the load is resistance;1A: when the load is inductance
The valve need have overtravel-limit organ to turn off the
load.

Replacement For

HONEYWELL T9275A-V1 TERMOSTAT HONEYWELL T9275A-V1 TERMOSTAT 
Please leave your enquiry here, we will reply as soon as possible.
Name*  
Company Name  
Product Interested  
Quantity  
Email*  
Contact No.*  
Ship to Name  
Shipping Address  
Attachment  
*only support gif, jpeg, jpg, png, pdf
Messages*  

Switch to Mobile Version
Recent Updates
Subscribe Newsletter